How do you stop a temporary site heater starting a fire?

Choose a heater without a flame, keep it uncovered and clear of anything that burns, feed it from a circuit sized for its load, and switch it off when nobody needs it. HSE’s construction fire guidance, HSG168, lists heaters among the ignition sources on a site. Its example of a safer choice is to replace naked-flame and radiant heaters with convector heaters or other heaters with no red element.

STAT

3 months is the longest interval NICEIC gives for inspecting and testing a fixed construction-site installation, and for testing RCDs with an instrument. Movable installations get checked more often, typically weekly. NICEIC published the summary in May 2023. Source: NICEIC via Voltimum, Environmental factors on construction sites

Key takeaways

Topic In brief
Heater type No flame and no combustion gases: electric or hydronic.
Placement Stable base, air intake and outlet clear, nothing combustible in the blowing direction.
Never Covered, bunched together, or used to dry clothes.
Power A circuit and plug rated for the heater, no daisy-chained or coiled leads.
Out of hours Off when not attended or needed, unless the fire risk assessment says otherwise.

Why are heaters a fire risk on a construction site?

A fire needs heat, fuel and oxygen, and a winter site has all three in the same room. HSG168, the third edition HSE published in July 2022, lists the heat sources a fire risk assessment should look for. Heaters are on that list by name: fixed or portable, electrical, and gas- or oil-fired heaters in temporary accommodation units.

The same list names unsuitable or damaged electrical installations, such as overloads. That matters because a large site heater is a heavy, long-running load on a temporary distribution board. A heater can start a fire in two ways: through its own heat reaching something that burns, or through the cable and socket that feed it.

The fuel is rarely far away. Packaging, insulation boards, timber, protective sheeting and work clothes all collect in the warm rooms where people want to be.

Which heaters does HSE point to?

HSE’s approach is substitution first. Paragraph 50 of HSG168 says to replace a potential ignition source with a safer alternative wherever possible, and its example is about heaters: replace naked flame and radiant heaters with fixed convector heaters or other types of heaters with no red element.

A flame also brings its own list of controls. For gas heaters in site accommodation, paragraph 181 asks for ventilation at high and low level, flame-failure devices, separate cylinders kept outside, the fuel turned off after use and an end-of-day check.

None of the site heaters in TSR’s range has a flame. The temporary electric heaters run on 230 V or 400 V and produce no flue gases. The hydronic heaters, such as the TSR WH30, take their heat from the district heating network through a heat exchanger, and a 230 V fan blows it into the building. TSR’s page for the WH30 says it plainly: no flame and no combustion gases.

That removes a whole class of risk, not all of it. An electric heater is still a hot appliance and a heavy electrical load.

Where should a site heater stand?

On a stable, level base, with air free to get in and out. TSR’s product pages, read in November 2026, put the same three rules on every fan heater: keep the air intake and outlet clear, never cover the heater, and place it well away from combustible materials. For the larger TSR-EH18, the page adds: do not place combustible material in the blowing direction.

HSG168 says the same from the other side. Paragraph 114 asks that lighting equipment, especially halogen lamps and heaters, is not inadvertently covered or left bunched together, so that it cannot ignite combustible material nearby or the structure itself. Paragraph 50 asks for ignition hazards and combustibles to be separated.

Two habits are worth naming. The first is drying wet gloves and jackets on a warm heater: HSG168 lists misuse of heaters for drying clothes among the issues workers should report, and its gas precautions say to keep heaters clear of obstructions such as clothing. The second is a heater pushed into a corner as the room fills with materials.

HSE gives no single clearance distance for heaters, and none should be invented. Use the distance in the manufacturer’s instructions and keep the blowing direction empty.

Is the power supply big enough for the heater?

Check it before the heater goes on. HSG168 paragraph 133 says electrical installations, temporary ones included, must have sufficient capacity for their intended use, be designed, installed, inspected and maintained by competent people, and meet BS 7671, which has a section on construction sites.

Paragraph 134 then lists the faults that start fires. Several of them are classic heater mistakes:

  • flat twin and earth cable used as an extension lead instead of a suitable flexible cable
  • overloaded sockets and multi-gang extensions
  • extension leads plugged into each other
  • coiled extension leads used without unwinding them fully
  • fuses or circuit breakers bypassed on purpose

A 9 kW heater on a coiled reel is a heater running on a hot lead. Our guide to how long a site extension lead can be explains why a reel must be fully unwound before it carries a heater.

The plug tells you what the heater needs. TSR’s 9 kW heaters use a 16 A CEE plug on 400 V, and NICEIC noted in May 2023 that plugs and socket-outlets from 16 A up to 125 A on construction sites should comply with BS EN 60309-2, the industrial plug standard. The EH18 needs a 400 V / 32 A outlet. HSG168 paragraph 135 adds that RCDs reduce the risk of fire from electrical faults but are no substitute for an installation that is properly designed, installed, inspected and maintained.

Leads laid across a walkway on the way to the heater are a trip hazard as well; our post on cable protectors and site walkways covers routing.

TSR site heaters compared

The figures below are from TSR’s product pages, read in November 2026.

Heater Supply Enclosure Safety notes on the product page
Electric heater 3kW 230 V, 1000 / 2000 / 3000 W IP24 Overheating protection, not for rain, away from combustibles
Electric heater 5kW 400 V / 16 A, 2500 / 5000 W IP24 Three settings incl. fan only
Electric heater 9kW and GAARD HEATER 9kW 400 V / 16 A, CEE 16 A plug IP24 Overheating protection, never cover
EH3 heater and drying fan 230 V, 2.1 / 2.8 kW IP44 10 A fuse at the low setting, 16 A at full; built-in kWh meter
TSR-EH18 400 V / 32 A, rated current 25 A, 9 / 18 kW IP44 Nothing combustible in the blowing direction
TSR WH30 hydronic 230 V, rated current 2.2 A; heat from district heating IP44 No flame, no combustion gases
Barrel heater 1500W 230 V, earthed socket, preferably with a 30 mA RCD IP67 At least 40 cm of the element under water

The enclosure rating decides where a heater can stand. IP24 takes splashing water but not rain; our post on IP ratings for site electrical equipment explains the numbers.

Heater fire check at the end of the shift

  • Need. Does the heater have to run tonight? If not, switch it off, as HSG168 asks for equipment that is not attended or being used.
  • Decide. If heat must run out of hours, for frost protection or drying, make it a decision in the fire risk assessment, not a habit.
  • Clear. Nothing on the heater, nothing in front of the outlet, no clothes drying on it.
  • Space. Materials delivered during the day have not crept into the blowing direction.
  • Supply. Plug fully home, lead unwound, no adapters or chained leads, no scorch marks.
  • Water. Barrel heaters: element still at least 40 cm under water after the day’s use.
  • Report. Anything damaged goes out of use and onto the inspection record.

Summary

Heaters are on HSE’s list of ignition sources on construction sites, and HSG168 points to substitution first: no naked flame, no red element. Electric and hydronic heaters remove the flame and the combustion gases, which leaves placement and power. Keep heaters uncovered, clear and away from anything that burns, feed them from a circuit and plug rated for the load, and switch them off when they are not needed. Tell TSR the size of the space and the supply you have, and we will size the heating for your site.

Frequently asked questions (FAQ)

Are temporary site heaters a fire risk?

Yes. HSE’s HSG168 lists heaters, fixed or portable, electrical or gas- and oil-fired, among the ignition sources a construction fire risk assessment should consider, along with overloaded and damaged electrical installations.

What type of heater does HSE recommend on site?

HSG168 gives replacing naked-flame and radiant heaters with fixed convector heaters, or other heaters with no red element, as its example of a safer alternative.

How far should a heater be from combustible materials?

HSG168 does not give a single distance. Follow the manufacturer’s instructions, keep the air intake and outlet clear, and keep combustible material out of the blowing direction.

Can I dry wet clothes on a site heater?

No. HSG168 lists misuse of heaters for drying clothes as an issue to report, and asks for heaters to be kept clear of obstructions such as clothing.

Can a site heater run overnight?

HSG168 asks for equipment to be turned off when it is not attended or being used. Where heat has to run out of hours, the fire risk assessment should say so and set the controls.

Can I run a 9 kW heater from an extension reel?

Only from a lead rated for the load and fully unwound. HSG168 lists coiled extension leads, overloaded sockets and leads plugged into each other among the common electrical fire faults.

Do electric site heaters need ventilation like gas heaters?

An electric or hydronic heater produces no combustion gases, so the gas precautions in HSG168, such as high and low ventilation and flame-failure devices, are not about them. Each heater still needs free air at its intake and outlet.